What is the occupancy classification of a restaurant, if it has an occupant load greater than 50 people?
What is the occupancy classification of a restaurant, if it has an occupant load greater than 50 people?A . BusinessB . KitchenC . MercantileD . AssemblyView AnswerAnswer: D Explanation: According to NFPA 101, Life Safety Code, and NFPA 5000, Building Construction and Safety Code, a restaurant with an occupant load...
What is a plans review checklist used for?
What is a plans review checklist used for?A . An all-inclusive code requirement list used by both the plan submitter and plan reviewerB . A complete list of mandatory code requirements for specific plan reviewsC . A guideline for contractors to follow in organizing documents for the plan reviewerD ....
What is the maximum common path of travel permitted in a sprinklered educational occupancy?
What is the maximum common path of travel permitted in a sprinklered educational occupancy?A . 20 ft (6 m)B . 75 ft (23 m)C . 100 ft (30 m)D . 200 ft (61 m)View AnswerAnswer: C Explanation: According to NFPA 101, Life Safety Code, the maximum common path of travel...
The automatic fire sprinkler deluge system depicted m the stage area of plan F2 0 supplies how many fire sprinklers?
Exhibit. The automatic fire sprinkler deluge system depicted m the stage area of plan F2 0 supplies how many fire sprinklers?A . 6B . 8C . 16D . 24View AnswerAnswer: D Explanation: Based on the plan F2.0, the automatic fire sprinkler deluge system depicted in the stage area supplies a...
On plan F0.1 the hydraulic calculations for the design were based on which of the following minimum flow criteria?
On plan F0.1 the hydraulic calculations for the design were based on which of the following minimum flow criteria?A . 740 gpm (2,800 lpm)B . 840 gpm (3,180 lpm)C . 1,040 gpm (3,937 ipm)D . 1,500 gpm (5,6781pm)View AnswerAnswer: C Explanation: On plan F0.1, the hydraulic calculations for the design...
On plan A12 what occupant load factor would you use?
Exhibit. On plan A12 what occupant load factor would you use?A . 30 ft2 (2 8 m2)B . 50 ft2 (4 6 m2)C . 100 ft2 (9 3 m2)D . 200 ft2 (18 6 m2)View AnswerAnswer: A Explanation: On plan A12, the occupant load factor to use is 30 ft²...
For the included figure, which dimension is the tread depth?
Exhibit. For the included figure, which dimension is the tread depth?A . AB . BC . CD . A+BView AnswerAnswer: B Explanation: The tread depth is the horizontal distance from the front edge of a stair tread to the back edge of the same tread, which corresponds to dimension "B"...
Draperies and decorations in day care occupancies shall comply with the provisions of which NFPA document?
Draperies and decorations in day care occupancies shall comply with the provisions of which NFPA document?A . NFPA701B . NFPA7Q3C . NFPA 704D . NFPA 705View AnswerAnswer: A Explanation: According to NFPA 101, Life Safety Code, draperies, curtains, and other similar furnishings and decorations in day care occupancies must comply...
What is the maximum travel distance to a single means of egress from a shoe store, if the store is not sprinklered and is less than 2.800 ft2 (260 m2) in size?
What is the maximum travel distance to a single means of egress from a shoe store, if the store is not sprinklered and is less than 2.800 ft2 (260 m2) in size?A . 25 ft (8 m)B . 50 ft (15 m)C . 75 ft (23 m)D . 100 ft...
The responsibility to promulgate rules that cover plan review is established by
The responsibility to promulgate rules that cover plan review is established byA . NFPA 1.B . NFPA 101.C . NFPA 170.D . NFPA 220.View AnswerAnswer: A Explanation: The responsibility to promulgate rules covering plan review is established by NFPA 1, Fire Code. NFPA 1 provides guidelines and regulations for the...