Where shall fire department connections on wet-pipe automatic sprinkler systems be located?
Where shall fire department connections on wet-pipe automatic sprinkler systems be located?A . On the system side of the water supply check valveB . On the suction side of booster pumpsC . On the supply side of the check valve in a single-riser systemD . Above the dry-pipe valve on...
A permit shall be required to store more than how many tires outside?
A permit shall be required to store more than how many tires outside?A . 200B . 300C . 400D . 500View AnswerAnswer: C Explanation: The outdoor storage of tires is regulated because tires pose significant fire hazards due to their combustibility and difficulty in extinguishment. According to NFPA 1, Fire...
The authorization to issue permits is granted by the
The authorization to issue permits is granted by theA . state legislature.B . authority having jurisdiction.C . Fire Inspection Handbook.D . NFPA 101, Life Safety Code.View AnswerAnswer: B Explanation: The authority having jurisdiction (AHJ) is the entity responsible for enforcing codes, standards, and regulations, including the authorization to issue permits....
The appropriateness of the safeguards required by the Life Safety Code to individual buildings and structures bears due regard to all EXCEPT which of the following?
The appropriateness of the safeguards required by the Life Safety Code to individual buildings and structures bears due regard to all EXCEPT which of the following?A . Age of the buildingB . The fire load of the occupancyC . Number of persons exposedD . Capabilities of the occupantsView AnswerAnswer: A...
To transfer Class I flammable liquids by pressurizing the tank, which of the following conditions must be met?
To transfer Class I flammable liquids by pressurizing the tank, which of the following conditions must be met? I. Inert gas is used to pressurize the tank. II. Air is used to pressurize the tank. III. A pressure relief device shall be provided. IV. An interlock shall be installed on...
What is the maximum travel distance to a fire extinguisher with a 20-B rating for an ordinary (moderate) type hazard?
What is the maximum travel distance to a fire extinguisher with a 20-B rating for an ordinary (moderate) type hazard?A . 30 ft (9.14 m)B . 50 ft (15.25 m)C . 75 ft (22.86 m)D . 100 ft (30.48 m)View AnswerAnswer: B Explanation: The travel distance to fire extinguishers for...
What is the rating for an interior finish material with a flame spread index of 100?
What is the rating for an interior finish material with a flame spread index of 100? A. Class A B. Class B C. Class C D. Class DView AnswerAnswer: B Explanation: Interior finish materials are rated based on their flame spread index (FSI), which measures how quickly flames spread across...
A document issued by the authority having jurisdiction for the purpose of authorizing performance of a specific activity would best be described as which of the following?
A document issued by the authority having jurisdiction for the purpose of authorizing performance of a specific activity would best be described as which of the following?A . PermissionB . ApprovalC . AcceptanceD . PermitView AnswerAnswer: D Explanation: The Authority Having Jurisdiction (AHJ) is responsible for authorizing specific activities to...
What is the minimum fire protection rating for a fire door in a 2-hour fire resistance-rated assembly that protects a refuse chute?
What is the minimum fire protection rating for a fire door in a 2-hour fire resistance-rated assembly that protects a refuse chute?A . ½ hourB . 1 hourC . 1½ hoursD . 2 hoursView AnswerAnswer: C Explanation: Fire doors in fire resistance-rated assemblies must have a fire protection rating proportionate...
What action should be taken by the inspector?
During an inspection, it is determined that the installation of a new suppression system is significantly different from the one approved during plans review. What action should be taken by the inspector?A . Issue a violation notice to the ownerB . Evaluate the installation for complianceC . Require a submittal...