Site icon Exam4Training

Huawei H19-402_V1.0 HCSP-Presales-Data Center Network Planning and Design V1.0 Online Training

Question #1

What is the channel width of Huawei Fusionmodule2000?

  • A . 1000mm
  • B . 1100mm
  • C . 1200mm
  • D . 1300mm

Reveal Solution Hide Solution

Correct Answer: C
Question #2

What is the earthquake resistance level of Huawei Fusionmodule2000 IT cabinet?

  • A . 7
  • B . 8
  • C . 9

Reveal Solution Hide Solution

Correct Answer: C
Question #3

What is the rated voltage of the single cell (CELL) in the VRLA battery?

  • A . 12V
  • B . 6V
  • C . 2V
  • D . 1V

Reveal Solution Hide Solution

Correct Answer: C
Question #4

The light-load dehumidification function of NetCoL5000-A042H full-cabinet row-level air-cooled variable frequency precision air conditioner supports stable dehumidification under the lowest () load. It can solve the problem of frequent start and stop of air conditioners and inability to dehumidify in low-load and high-humidity environments, and reduce the risk of condensation in the computer room.

  • A . 0.05
  • B . 0.1
  • C . 0.15
  • D . 0.2

Reveal Solution Hide Solution

Correct Answer: B
Question #5

What configuration methods does the FusionModule800 UPS support?

  • A . N/2N
  • B . N/N+1/2N
  • C . N/N+1

Reveal Solution Hide Solution

Correct Answer: B
Question #6

Does the FusionModule800 channel have a skylight?

  • A . No
  • B . Yes

Reveal Solution Hide Solution

Correct Answer: A
Question #7

FusionModule1000A V2R3 version 40-foot IT solution N+X redundancy with IBATTWERY configuration, how many IT cabinets can it provide?

  • A . 5
  • B . 6
  • C . 7
  • D . 8
  • E . 9

Reveal Solution Hide Solution

Correct Answer: C
Question #8

What is the power supply architecture of the new row-level half-cabinet chilled water?

  • A . Single power supply
  • B . Dual power supply
  • C . AB are both correct
  • D . Others

Reveal Solution Hide Solution

Correct Answer: C
Question #9

Which of the following humidification forms consumes the least energy?

  • A . Wet film humidification
  • B . Electrode humidification
  • C . Infrared humidification

Reveal Solution Hide Solution

Correct Answer: A
Question #10

What is the protection level of PDU8000 precision power distribution cabinet?

  • A . IP20
  • B . IP21
  • C . IP30
  • D . IP40

Reveal Solution Hide Solution

Correct Answer: A

Question #11

What is the energy saving effect of Huawei’s Icooling?

  • A . 15%
  • B . 10%
  • C . 8%
  • D . 5%

Reveal Solution Hide Solution

Correct Answer: A
Question #12

What is the maximum power of the IT cabinet of FusionModule500 & FusionModule800?

  • A . 3KVA
  • B . 9KVA
  • C . 7KVA
  • D . 5KVA

Reveal Solution Hide Solution

Correct Answer: C
Question #13

When configuring temperature control products, if the temperature at the project site is -10-30 degrees Celsius, which of the following working conditions should be preferred?

  • A . Wide temperature range (-40-55 degrees Celsius)
  • B . T1 (-20-45 degrees Celsius)
  • C . T3 (-20-55 degrees Celsius)
  • D . Ultra-low temperature (-40-45 degrees Celsius)

Reveal Solution Hide Solution

Correct Answer: B
Question #14

In which of the following areas is the AHU solution least effective?

  • A . ***
  • B . Beijing
  • C . Harbin
  • D . Hainan

Reveal Solution Hide Solution

Correct Answer: D
Question #15

What sensor does FusionModule2000 use to detect whether the air conditioner is leaking?

  • A . Multifunctional sensor
  • B . Infrared sensor
  • C . Temperature sensor
  • D . Water sensor

Reveal Solution Hide Solution

Correct Answer: D
Question #16

Which of the following are optional in the typical configuration of FusionModule500?

  • A . PAD, SMS alarm, video, mobile APP, switch
  • B . PAD, SMS alarm, video, flooding, smoke detection
  • C . PAD, SMS alarm, mobile phone APP, flooding, door magnet

Reveal Solution Hide Solution

Correct Answer: A
Question #17

The UPS system is equipped with 32 12V batteries. What is the floating charge voltage set by the UPS?

  • A . 432V
  • B . 451V
  • C . 540V
  • D . 564V

Reveal Solution Hide Solution

Correct Answer: A
Question #18

Which is the fire extinguishing measures that can be adopted in Class A computer rooms?

  • A . Gas fire extinguishing system
  • B . Water mist fire extinguishing system
  • C . Automatic sprinkler system
  • D . All of the above

Reveal Solution Hide Solution

Correct Answer: A
Question #19

What is the output power factor of UPS2000-A-(1K-3K)?

  • A . 0.7
  • B . 0.8
  • C . 0.9
  • D . 0.99

Reveal Solution Hide Solution

Correct Answer: B
Question #20

Which of the following UPS does not have a neutral line?

  • A . UPS5000-H
  • B . UPS5000-E
  • C . galaxy5000
  • D . APM150

Reveal Solution Hide Solution

Correct Answer: A

Question #21

What is the UPS2000-G 6-20k host operation interface? which can display the system status in real time.

  • A . LED
  • B . LCD
  • C . Touch screen
  • D . Remote network management

Reveal Solution Hide Solution

Correct Answer: B
Question #22

Considering the low load rate of the UPS system, the UPS5000-E is designed with an intelligent sleep function, which can increase the system load rate and keep the system running efficiently. When the UPS5000E is in intelligent sleep mode, how many power modules are redundant?

  • A . 2
  • B . 1
  • C . 0

Reveal Solution Hide Solution

Correct Answer: B
Question #23

What is the static load of the FusionModule200 cabinet?

  • A . 1500
  • B . 1800
  • C . 2000
  • D . 2400

Reveal Solution Hide Solution

Correct Answer: B
Question #24

Which of the following is incorrect about the function description of iMiManager in FusionModule2000v3.0?

  • A . Support automatic asset configuration
  • B . When the server is listed, the best server location can be recommended
  • C . Can display capacity data such as space, power distribution, and cooling
  • D . All of the above

Reveal Solution Hide Solution

Correct Answer: D
Question #25

When selecting the extended dry contact card and the backfeed protection card for UPS5000-E, which of the following options should also be selected?

  • A . ECM expansion frame
  • B . IP21 components
  • C . Dry contact card socket

Reveal Solution Hide Solution

Correct Answer: A
Question #26

What line-in methods does UPS5000-A-400/500K support?

  • A . Downstream line
  • B . Upper line
  • C . Up and down wiring compatible

Reveal Solution Hide Solution

Correct Answer: C
Question #27

What is the humidifier used by the row-level chilled water intelligent temperature control product NetCol5000-C032H?

  • A . Electrode
  • B . Infrared
  • C . Wet film
  • D . Ultrasound

Reveal Solution Hide Solution

Correct Answer: C
Question #28

UPS5000-E only needs to be equipped with () to easily realize the 2N power supply system, which is simple and convenient to operate?

  • A . BSC cable
  • B . Synchronous Controller
  • C . BSC control panel
  • D . Parallel card

Reveal Solution Hide Solution

Correct Answer: A
Question #29

Which of the following is incorrect about the reliability of NetCol5000-C row-level air conditioners?

  • A . Dual power supply, two power supplies use automatic switching mode
  • B . Operators, large corporate headquarters and other large data centers prefer this type of air conditioner.
  • C . Small and medium-sized enterprises more often use Netcp15000-A air conditioner with multiple fans for air supply: it can be maintained online.
  • D . It cannot be used in scenarios without raised floors because the condensate drainage cannot be connected to the pipes.

Reveal Solution Hide Solution

Correct Answer: D
Question #30

What power input methods does FusionModule800 support?

  • A . Single or dual
  • B . Dual-channel
  • C . Single channel

Reveal Solution Hide Solution

Correct Answer: A

Question #31

What is the lowest outdoor ambient temperature that the FusionModule800 air conditioner can support?

  • A . -20 degrees Celsius
  • B . -40 degrees Celsius
  • C . 0 degrees Celsius

Reveal Solution Hide Solution

Correct Answer: B
Question #32

Which of the following descriptions of the eLight function of the intelligent module status indicator in FusionModule2000v3.0 is correct?

  • A . The door frame indicator light eLight is only a decorative atmosphere rendering function
  • B . Door frame indicator lights can be associated with alarm status
  • C . Door frame indicator light eLight is a module lighting function
  • D . None of the above is correct

Reveal Solution Hide Solution

Correct Answer: B
Question #33

For cabinets (racks) arranged in rows, when their length exceeds (), additional channels should be added between two channels, and channels should be set up at both ends: when the distance between two channels exceeds (), channels should be added directly between the two channels.

  • A . 6m, 15m
  • B . 6m, 20m
  • C . 8m, 15m
  • D . 8m, 20m

Reveal Solution Hide Solution

Correct Answer: A
Question #34

UPS5000-E has a wide voltage and frequency input range, which can be used in harsh power grid environments and extend battery life. What is the input voltage range of UPS5000-E at full load?

  • A . 138-485V
  • B . 305-485V
  • C . 105-485V

Reveal Solution Hide Solution

Correct Answer: A
Question #35

What are the maximum number of cabinets in FusionModule500 and FusionModule800?

  • A . 10,6
  • B . 6, 2
  • C . 9,5
  • D . 4, 10

Reveal Solution Hide Solution

Correct Answer: D
Question #36

The UPS5000-series modular UPS product features are similar to which of the following product models?

  • A . Hipulse-u
  • B . 8O-NET
  • C . NXr
  • D . APM

Reveal Solution Hide Solution

Correct Answer: D
Question #37

Which of the following features are standard features of NETCOL8000-C air conditioner?

  • A . Dual power supply
  • B . Water sensor
  • C . G4 grade filter
  • D . Humidification function

Reveal Solution Hide Solution

Correct Answer: C
Question #38

UPS5000-E 100kVA, which of the following input switches is most suitable for the machine?

  • A . 125A
  • B . 80A
  • C . 160A
  • D . 200A

Reveal Solution Hide Solution

Correct Answer: D
Question #39

UPS500-A-400/500K can support a maximum of () parallel connections and has good scalability.

  • A . 4
  • B . 2
  • C . 3
  • D . 6

Reveal Solution Hide Solution

Correct Answer: A
Question #40

Assume that the discharge power specified in a battery specification is 400W@1.67V@15min, and if the system requirement is 1400W. Which of the following number of battery packs is selected?

  • A . 3
  • B . 4
  • C . 5

Reveal Solution Hide Solution

Correct Answer: B

Question #41

UPS5000-A/E 400KVA and above models are divided into standard version and enhanced version. The standard version is equipped with () isolation switch.

  • A . Main input
  • B . Bypass Input
  • C . Repair
  • D . Output

Reveal Solution Hide Solution

Correct Answer: C
Question #42

When the NetEco management system intervenes in third-party devices outside the micromodule, what kind of monitoring hardware is usually used to access it?

  • A . ECC500 collector
  • B . ECC800 Collector
  • C . Serial port server
  • D . None of the above

Reveal Solution Hide Solution

Correct Answer: A
Question #43

When using a single RH5885 server, how many measurement points can the NetEco management system support to achieve centralized management of multiple data centers?

  • A . 20
  • B . 40
  • C . 50
  • D . 100

Reveal Solution Hide Solution

Correct Answer: A
Question #44

A project requires the management system to access a third-party generator set, two smart meters (same model), and two precision air conditioners (same model). How many third-party equipment access fees does the management system need to report?

  • A . 1
  • B . 3
  • C . 5
  • D . None of the above

Reveal Solution Hide Solution

Correct Answer: B
Question #45

The number of batteries in traditional UPS cannot be adjusted, and the battery maintenance cost is high. If one battery is damaged, the entire battery group may need to be replaced. The number of batteries in UPS5000-A can be adjusted, so what is the adjustable range?

  • A . 30-40
  • B . 34-40
  • C . 36-40
  • D . 32-40

Reveal Solution Hide Solution

Correct Answer: A
Question #46

How many poles of circuit breaker are generally used for the external maintenance bypass of UPS system?

  • A . 3
  • B . 1
  • C . 4
  • D . 2

Reveal Solution Hide Solution

Correct Answer: A
Question #47

Huawei Technologies Co., Ltd. is compliant with GB50174-2008 standard ( ) is compliant with GB50174-2017 standard ( ).

  • A . Participating units, Auditing unit
  • B . Participating units, participating units
  • C . Auditing unit, Auditing unit
  • D . Auditing unit, Participating units

Reveal Solution Hide Solution

Correct Answer: C
Question #48

Which of the following are the types of channel doors of Huawei Fusionmodule2000V3.0?

  • A . Sliding door
  • B . Revolving Door
  • C . Electric door
  • D . Both

Reveal Solution Hide Solution

Correct Answer: D
Question #49

Which of the following is the battery type supported by UPS2000-G?

  • A . VRLA
  • B . Lithium battery
  • C . Nickel-cadmium battery
  • D . Flywheel

Reveal Solution Hide Solution

Correct Answer: A
Question #50

The NetEco management system adopts a large-capacity design architecture, which can support the access of massive devices and the access of up to () 10,000 measurement points using a single X86 server. At the same time, the system operates smoothly and the CPU utilization rate is no higher than ().

  • A . 50, 70
  • B . 100, 70
  • C . 50, 90
  • D . 100, 90

Reveal Solution Hide Solution

Correct Answer: D
Exit mobile version