Huawei H19-371_V1.0-ENU HCS-Pre-sales-Digital Power V1.0 Online Training

Question #1

If the UPS5000-A-400/500K is configured with a set of 40 12V batteries, how many battery inspection instruments do you need to configure? ( )

  • A . 1
  • B . 2
  • C . 3
  • D . 40

Reveal Solution Hide Solution

Correct Answer: B
Question #2

Does the FusionModule800 channel have a skylight?

  • A . have
  • B . None

Reveal Solution Hide Solution

Correct Answer: B
Question #3

The type of circuit breaker used in the sub-circuit of the PDU8000 precision power distribution cabinet. ( )

  • A . Disconnect switch
  • B . Molded Case Circuit Breakers
  • C . Miniature circuit breakers
  • D . Frame circuit breaker

Reveal Solution Hide Solution

Correct Answer: C
Question #4

What is the maximum IT load supported by the FusionModule2000 integrated UPS? ( )

  • A . 125KW
  • B . 150KW
  • C . 75KW
  • D . 50KW

Reveal Solution Hide Solution

Correct Answer: A
Question #5

Which of the following is the refrigerant type of Huawei NetCol in-line air-cooled air conditioner ( )?

  • A . R22
  • B . R410A
  • C . Freon

Reveal Solution Hide Solution

Correct Answer: B
Question #6

Regarding the Fusion module surveillance camera, which of the following statements is false? ( )

  • A . Any number of cameras can be plugged into the ETH socket
  • B . The camera power supply mode is PoE power supply
  • C . The camera can be directly connected to the switch powered by PoE.
  • D . The camera data can be stored by TF card or hard disk recorder (NVR: Network Video Recorde)

Reveal Solution Hide Solution

Correct Answer: A
Question #7

Compared with the chilled water scheme, which of the following is not an advantage of AHU ( )

  • A . Lower PUE
  • B . Easier deployment
  • C . Less difficult operation and maintenance
  • D . Wider range of applications

Reveal Solution Hide Solution

Correct Answer: D
Question #8

The output power factor of UPS2000-G-(6K-20K) is ( ), which is suitable for new IT loads and significantly improves the load capacity of the system.

  • A . 0.7
  • B . 0.8
  • C . C. 0.9
  • D . 0.99

Reveal Solution Hide Solution

Correct Answer: C
Question #9

Huawei iManager NetEco6000 can be accessed by Huawei’s ( ) system

  • A . XXX
  • B . esight
  • C . XXXX

Reveal Solution Hide Solution

Correct Answer: B
Question #10

The single cooling capacity range of the water-cooled centrifugal unit is:

  • A . 100-1000kW
  • B . 200-2000kW
  • C . 300-3000kW
  • D . 500-5000kW

Reveal Solution Hide Solution

Correct Answer: C

Question #11

The cell of Huawei Smartli lithium battery is ( )

  • A . NCM
  • B . LFP
  • C . Ni-Cd

Reveal Solution Hide Solution

Correct Answer: B
Question #12

Is the channel type of the typical configuration of FusionModule800 a cold aisle or a hot aisle? ( )

  • A . Hot and cold aisle
  • B . Hot Aisle

Reveal Solution Hide Solution

Correct Answer: A
Question #13

What are the incoming line methods supported by UPS5000-A-400/500K? ( )

  • A . Downstream
  • B . Top entry line
  • C . Compatible with upper and lower incoming lines

Reveal Solution Hide Solution

Correct Answer: C
Question #14

At which of the following voltages the lead-acid battery is already in a dangerous state ( )

  • A . 1.67
  • B . 2.25
  • C . 2.35
  • D . 2.45

Reveal Solution Hide Solution

Correct Answer: D
Question #15

Which are standard configurations in the typical configuration of FusionModule800? (

  • A . Smoke sensor, door sensor, pad, water immersion, simple wiring trough, video
  • B . Temperature and humidity, door sensor, pad, water flood, video, mobile APP
  • C . Smoke sensor, temperature and humidity, pad, SMS alarm, mobile APP, automatic pop-up door

Reveal Solution Hide Solution

Correct Answer: C
Question #16

The NetEco6000 management system supports access to third-party equipment to achieve centralized management of the computer room; then, when monitoring which of the following equipment is connected to third-party equipment,

it is necessary to pay the RM bill and report the third-party equipment access fee? (

  • A . Huawei UPS 5000E
  • B . Huawei Power Supply TP48300
  • C . Emerson Air Conditioning
  • D . None of the above is true

Reveal Solution Hide Solution

Correct Answer: C
Question #17

In FusionModule2000, how to adapt the skylight when the column occupies the closed passage space in the scene around the column?

  • A . Customized tempered glass flip skylight
  • B . Field machining with control skylight
  • C . On-site cutting with plexiglass adjustable skylight
  • D . Sealed with special adjustable sealing plate for skylight

Reveal Solution Hide Solution

Correct Answer: D
Question #18

When the NetEco management system is sold in the market, which of the following situations does not need to submit RM to the management system RAT for decision-making? ( )

  • A . When there are three-party equipment access requirements in the project.
  • B . When there is non-standard function customization in the project, the existing products cannot meet it.
  • C . When supporting FusionModule products for sale
  • D . When large-scale DC project network management is sold separately.

Reveal Solution Hide Solution

Correct Answer: C
Question #19

Fusionmodule2000 IT cabinet seismic rating? ( )

  • A . 7
  • B . 8
  • C . 9

Reveal Solution Hide Solution

Correct Answer: C
Question #20

Which of the following statements is false about surveillance cameras?

  • A . Less than 4 cameras can be connected to the ETH socket
  • B . The camera power supply mode is PoE power supply
  • C . The camera can be directly connected to the switch powered by PoE
  • D . Camera data can be stored through TF card or VCN500
  • E . The number of cameras configured is the same as the number of control sunroofs

Reveal Solution Hide Solution

Correct Answer: E

Question #21

What is the static load of the FusionModule2000 cabinet in KG?

  • A . 2400
  • B . 1800
  • C . 1500
  • D . 2000

Reveal Solution Hide Solution

Correct Answer: A
Question #22

What are the ways of piping in FusionModule800? ( )

  • A . Compatible with up and down pipes
  • B . Down the tube
  • C . Up the tube

Reveal Solution Hide Solution

Correct Answer: A
Question #23

The maximum charging capacity of UPS5000-E is ( )

  • A . 40%
  • B . 20%
  • C . 10%
  • D . 30%

Reveal Solution Hide Solution

Correct Answer: A
Question #24

The row-level chilled water intelligent temperature control product NetCol 5000-C032H adopts the form of running pipes ( )

  • A . Up the tube
  • B . Down the tube
  • C . Pipe up and down
  • D . Side run.

Reveal Solution Hide Solution

Correct Answer: B
Question #25

The UPS used by FusionPower (prefabricated power module) is ( ).

  • A . UPS5000-E
  • B . UPS5000-A
  • C . UPS5000-H
  • D . PS5000-S

Reveal Solution Hide Solution

Correct Answer: C
Question #26

When the single cell voltage in the battery pack reaches ( ), it means that the battery pack is already in a risky state

  • A . 1.67V
  • B . 2.25V
  • C . 2.35V
  • D . 2.42V

Reveal Solution Hide Solution

Correct Answer: D
Question #27

The minimum ambient temperature used by FusionModule800 and FusionModule500 is ( ).

  • A . -20°C.
  • B . 0°C.
  • C . -40°C.
  • D . Below -40°C

Reveal Solution Hide Solution

Correct Answer: B
Question #28

UPS2000-G 1~3kVA supports ( ) parallel.

  • A . 0
  • B . 2
  • C . 3
  • D . 4

Reveal Solution Hide Solution

Correct Answer: A
Question #29

UPS2000-G 6~20kVA maximum support ( ) parallel, good scalability.

  • A . 0
  • B . 2
  • C . 3
  • D . 4

Reveal Solution Hide Solution

Correct Answer: D
Question #30

When a system is configured with a battery backup time of 15 minutes, the discharge termination voltage of the battery cell should be selected ( )

  • A . 1.60V
  • B . 1.67V
  • C . 1.75V
  • D . 1. 80V

Reveal Solution Hide Solution

Correct Answer: B

Question #31

Among the following models, the one with the widest input frequency range is ( )

  • A . Galaxy5000
  • B . NXR
  • C . 9390
  • D . UPS5000-A

Reveal Solution Hide Solution

Correct Answer: D
Question #32

For the UPS5000-A system, which of the following battery configurations is unreasonable: ( ) (multiple choice)

  • A . 32 12V batteries
  • B . 37 12V batteries
  • C . 40 12V batteries
  • D . 42 12V batteries

Reveal Solution Hide Solution

Correct Answer: B
Question #33

FusionModule2000 maximum number of counters ( )

  • A . 24
  • B . 36
  • C . 50
  • D . 48

Reveal Solution Hide Solution

Correct Answer: C
Question #34

What is the minimum outdoor ambient temperature that the FusionModule800 air conditioner can support? ( )

  • A . -20
  • B . -40
  • C . 0

Reveal Solution Hide Solution

Correct Answer: B
Question #35

FusionModule500&FusionModule800 display brand optional ( )

  • A . Blu-ray
  • B . Huawei Honor
  • C . apple
  • D . Samsung

Reveal Solution Hide Solution

Correct Answer: B
Question #36

How many cabinets can a single row of FusionModule2000 support? ()

  • A . 48
  • B . 12
  • C . 36
  • D . 24

Reveal Solution Hide Solution

Correct Answer: D
Question #37

UPS5000-A-400/500K can support up to ( ) parallel machine, with good scalability. ()

  • A . 4
  • B . 2
  • C . 3
  • D . 6

Reveal Solution Hide Solution

Correct Answer: D
Question #38

"Data Center Design Specifications" GB50174-2017 stipulates that when selecting a site, a cooling data center should have sufficient water sources.

  • A . Direct ventilation cooling method
  • B . Indirect fresh air cooling method
  • C . Water evaporative cooling method
  • D . Chilled water cooling method

Reveal Solution Hide Solution

Correct Answer: C
Question #39

UPS5000-E only needs to select ( ), it can easily realize 2N power supply system, and the operation is simple and convenient. .

  • A . BSC cable
  • B . Sync Controller
  • C . BSC Control Board
  • D . Parallel card

Reveal Solution Hide Solution

Correct Answer: A
Question #40

The NetEco management system supports dispatching corresponding work orders for a certain alarm to track the entire processing process.

What type of work order is this? (

  • A . Asset Work Order
  • B . Change Work Order
  • C . Alert Ticket
  • D . Business Tickets

Reveal Solution Hide Solution

Correct Answer: C