What two tasks should be completed to troubleshoot this issue?

A new M1000e is being deployed in the data center. All initial power and data cabling is complete. The engineer checks the CMC Chassis Health and sees that one of the six PSUs displays as Failed (No AC). An AC cable is connected, and the power distribution unit produces good AC output.

What two tasks should be completed to troubleshoot this issue? (Choose two. )
A . Verify all PSUs are connected to the same voltage.
B . Confirm System Input Power Cap is NOT set too low.
C . Replace AC cable.
D . Set AC redundancy to 4+1.

Answer: A,C